Glossary · Heating, cooling & ventilation
COP (coefficient of performance)
Also called: COP at 5°F · heating COP
Heat delivered divided by electricity used at a given moment; a COP of 3 means three units of heat for each unit of electricity.
What it means
Electric baseboards and furnaces turn electricity into heat one-for-one, so their COP is about 1. Heat pumps reach COPs of 2 to 5 in mild weather because they move heat instead of making it, but COP falls as the outdoor temperature drops. Seasonal ratings such as HSPF average this over a whole winter.
Why it matters in an audit
COP at cold temperatures, such as −15°C (5°F), shows how cheaply a heat pump will run in your coldest weather and helps find the economic balance point against gas or oil.
Typical numbers
Reference values with their sources. Your auditor’s report gives the figure for your own house.
| What | Value | Source |
|---|---|---|
| Air-source heat pumps (NRCan) | 2.0–5.4 at 46°F (8°C); 1.1–3.7 at 18°F (−8°C) | natural-resources.canada.ca ↗ |
| Ground-source heat pumps (NRCan) | About 3 in the coldest months | natural-resources.canada.ca ↗ |
| ENERGY STAR Cold Climate minimum | 1.75 at 5°F (−15°C) | energystar.gov ↗ |