Glossary · Heating, cooling & ventilation

Cold-climate heat pump (ccASHP)

Also called: cold-climate air-source heat pump · ENERGY STAR Cold Climate · cold climate certified

An air-source heat pump built to keep heating efficiently in deep cold, usually verified by ENERGY STAR Cold Climate or the NEEP list.

What it means

Cold-climate models use variable-speed (inverter) compressors and are tested to hold more capacity and efficiency at −15°C (5°F). The main references are ENERGY STAR's Cold Climate designation and the NEEP Cold Climate Air Source Heat Pump Specification and product list, which publishes low-temperature data used for sizing. Rebate programs often require a listed model.

Why it matters in an audit

In heating-dominated climates, a true cold-climate model can carry most or all of the winter load, reducing reliance on expensive auxiliary heat.

Typical numbers

Reference values with their sources. Your auditor’s report gives the figure for your own house.

What Value Source
ENERGY STAR Cold Climate (spec 6.2) COP ≥ 1.75 at 5°F (−15°C); capacity at 5°F ≥ 70% of capacity at 47°F; HSPF2 ≥ 8.5 ductless or ≥ 8.1 ducted and packaged; SEER2 ≥ 15.2 energystar.gov ↗
NEEP ccASHP Specification v4.0 (effective Jan 1, 2023) COP above 1.75 at 5°F at maximum capacity; variable-capacity compressor; HSPF2 above 7.7 ducted or 8.5 ductless; SEER2 above 15 neep.org ↗
NEEP v5.0 proposal (released July 7, 2026; comments closed Aug 28, 2026) Would rely on ENERGY STAR Cold Climate certification or CEE Tier 1 Path A instead of NEEP's own thresholds; NEEP's page still lists v5.0 as coming, with no effective date (checked 2026-10-26) neep.org ↗
NEEP's target climates IECC climate zone 4 and colder neep.org ↗

Sources